Detailed Setup—Transducer Block
July 2013
Valve and Actuator
TB > Configure/Setup > Detailed Setup > Valve and Actuator
Field Communicator
Valve
D Valve Manufacturer—Enter the identification number of the manufacturer of the valve (VALVE_MAN_ID [25]) on
which the instrument is mounted. Select from the drop‐down list or enter the manufacturer's identification number
as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100.
D Valve Model Number—Enter the valve model number (VALVE_MODEL_NUM [26]), (design letter or type number)
for the valve on which the instrument is mounted.
D Valve Serial Number—Enter the serial number of the valve (VALVE_SN [27]) on which the instrument is mounted.
D Valve Style—Enter the type of valve (VALVE_TYPE [28]), sliding‐stem or rotary, on which the instrument is mounted.
D Valve Size—Enter the size of the valve (VALVE_SIZE [83.1]) on which the instrument is mounted.
D Valve Class—Enter the valve pressure class rating (VALVE_CLASS [83.2]).
D Rated Travel—Enter the valve rated travel (RATEDTRAVEL [83.3]) in inches or mm for sliding-stem valves, or in
degrees of rotation for rotary valves.
D Actual Travel—Enter the actual travel (ACTUAL_TRAVEL [83.4]) in inches or mm for sliding-stem valves, or in degrees
of rotation for rotary valves.
D Shaft Stem Diameter—Enter the valve stem diameter (SHAFT_STEM_DIA [83.5]) in inches or millimeters.
D Packing Type—Enter the valve packing construction (PACKING_TYPE [83.6]).
D Inlet Pressure—Enter the valve inlet pressure (INLET_PRESSURE [83.7]).
D Outlet Pressure—Enter the valve outlet pressure (OUTLET_PRESSURE [83.8]) in psig, kPa, Bar, inHg, inH
Trim
D Seat Type—Enter the valve seat type (SEAT_TYPE [84.1]).
D Leak Class—Enter the valve leak class (LEAK_CLASS [84.2]).
D Port Diameter—Enter the valve port diameter (PORT_DIAMETER [84.3]) in inches or mm.
D Port Type—Enter the valve port type (PORT_TYPE [84.4]).
D Flow Direction—Enter the flow direction (FLOWDIRECTION [84.5]) through the valve.
D Push Down To—Enter the effect on valve movement when the stem is moved down (PUSH_DOWN_TO [84.6]).
D Flow Tends To—Enter the effect on valve travel with increasing flow (FLOW_TENDS_TO [84.7]).
D Unbalanced Area—Enter the valve unbalanced area (UNBALANCED_AREA [84.8]) in in
82
Instruction Manual
D103412X012
O, or kg/cm
2
2
2
or mm
.
2
.

Hide quick links: