Fisher FIELDVUE DVC6200f Instruction Manual page 124

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—AO Function Block
July 2013
Table 4‐25. Analog Output Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Grant Deny
GRANT_DENY
GRANT
DENY
I/O Options
IO_OPTS
Status Options
STATUS_OPTS
Readback
READBACK
Cascade Input
CAS_IN
Setpoint Rate Down
SP_RATE_DN
Setpoint Rate Up
SP_RATE_UP
Setpoint High Limit
SP_HI_LIM
Setpoint Low Limit
SP_LO_LIM
AO Channel
CHANNEL
Fault State Time
FSTATE_TIME
122
Index
RO /
Block
Number
RW
Mode
13
0: Program
13.1
RW
ALL
1: Tune
2: Alarm
13.2
RW
ALL
3: Local
1: SP tracks PV in Man
3: SP tracks PV in LO or
Iman
4: SP Track retained
target in Man or LO
5: Increase to Close
6: Fault State to value
14
OOS
7: Use Fault State
value on restart
8: Target to Man if
Fault State activated
9: Use PV for
BKCAL_OUT
4: Propagate Failure
15
OOS
Backward
Status
16
RO
N/A
Value
Status
17
ALL
Value
Positive, 0 disables
18
ALL
rate limiting PV units
Positive, 0 disables
19
ALL
rate limiting PV units
20
ALL
PV Scale +/- 10%
21
ALL
PV Scale +/- 10%
22
OOS
1=Setpoint
23
ALL
Positive, seconds
Initial
Range
Value
All bits: 0
All bits: 0
0=freeze
1=go to Fault State
All bits: 0
value
0=SP
1=PV
All bits: 0
Dynamic
BAD:
NC:
const
0
+INF
+INF
100
0
1=Setpoint
0
-Continued-
Instruction Manual
D103412X012
Description
Data Type: DS‐70
Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block.
GRANT: 1 = granted, 0= N/A
DENY: 1 = denied, 0 = N/A
Data Type: Bit String (2 byte)
0=disable
1=enable
Allows you to select the type of tracking and the
output value when a fault condition occurs.
Data Type: Bit String
0=disable
1=enable
Options the user may select for the block
processing of status.
Data Type: DS‐65
Readback is the de‐characterized valve position as
reported by the transducer block parameter
FINAL_POSITION_VALUE [17]. This correlates with
the AO block parameter OUT [9], which is the
setpoint to the transducer. READBACK is the
simulated input if SIMULATE is enabled or the
transducer block feedback if SIMULATE is disabled.
Data Type: DS‐65
The setpoint value from another function block.
Data Type: Float
Ramp rate for downward set point changes. When
the ramp rate is set to zero, the set point is used
immediately.
Data Type: Float
Ramp rate for upward set point changes. When the
ramp rate is set to zero, the setpoint is used
immediately.
Data Type: Float
The highest set point value allowed. SP_HI_LIM
must be greater than SP_LO_LIM.
Data Type: Float
The lowest set point value allowed. SP_LO_LIM
must be less than SP_HI_LIM.
Data Type: Unsigned16
Defines which transducer parameter receives the
AO output. Select Setpoint to control valve
position.
Data Type: Float
Time from failure detection to reaction if failure still
exists.