Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Self Test Status
SELFTEST_STATUS
Health Index
HEALTH_INDEX
Reserved A
RESERVED_A
106
Index
RO /
Mode
Number
RW
78
RO
N/A
0:
2: Integrator Limited Low
3: Integrator Limited
High
4: Travel Sensor Span
Error
5: MLFB Error
7: Travel Sensor High
Error
8: Travel Sensor Low Error
9: Pressure Sensor B
10: Pressure Sensor A
11: Supply Pressure
Sensor
13: IOP Failure
14: Drive Current
15: Simulate Jumper ON
79
RO
N/A
0 - 100
80
RW
ALL
Range
Initial Value
All bits: 0
100
N/A
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Bit String (2 byte)
0=inactive
1=active
Indicates the status of the
instrument self test.
Integrator Limited Low: Indicates
the integrator reached its limit and
cannot move the valve any further.
High valve friction may cause this
situation.
Integrator Limited High:
Indicates the integrator reached its
limit and cannot move the valve any
further. High valve friction may
cause this situation.
Travel Sensor Span Error:
Indicates that span between the
endpoints of travel are not far
enough apart. This error is reported
during automatic calibration.
MLFB Error: Indicates that the Minor
Loop Feedback sensor gave a
non‐valid value during automatic
calibration.
Travel Sensor High Error:
Indicates the travel sensor has
reported a travel position that is
significantly above the normal
operating range, and has failed.
Travel Sensor Low Error: Indicates
the travel sensor has reported a
travel position that is significantly
below the normal operating range,
and has failed.
Pressure B Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
Pressure A Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
Supply Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
IOP Failure: Indicates the I/O
processor has failed.
Drive Current: Indicates that the
Drive Current has exceeded the
Drive Current Alert Point for more
than the Drive Current Alert Time.
Simulate Jumper ON: Indicates the
simulate jumper is connected to the
DVC6200f between the two AUX
terminals.
Data Type: Uint8
Represents overall health of device.
100 is perfect, 0 is completely bad.
N/A
Settings for DVC6200f will range
from 10 to 100.
Data Type: Array, 118 x Unit8
SETUP
Reserved