D103412X012
Table 4‐77. Channel Selection for the Discrete Input Function Block
Selection
Transducer Block Parameter
23
TRAVEL_D
24
INST_ALERTS_ACTIVE:PROX_ACTIVE
25
INST_ALERTS_ACTIVE:PROX_ACTIVE
26
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
27
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
28
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
29
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
30
INST_ALERTS_ACTIVE:PROX_ACTIVE
31
INST_ALERTS_ACTIVE:PROX_ACTIVE
32
INST_ALERTS_ACTIVE:PROX_ACTIVE
33
INST_ALERTS_ACTIVE:PROX_ACTIVE
1. Refer to table 4‐14 for parameter descriptions.
2. See pages 74 and 76, Travel ALerts and Prox Alerts, for information on accessing these alerts. Refer to Appendix F for information on accessing these alerts through DeltaV.
Open/Closed Limit Switch
Channels 24 and 25 provide valve open and closed limit switch functionality for the DI block. These channels will
detect if the valve position is more than the Travel Open Alert Point for open detection or less than the Travel Closed
Alert Point for closed detection. These channels provide an adjustable deadband to clear the detected position.
0= Not Active, 1= Active
Variable Limit Switch
Channels 26 through 29 provide variable limit switch functionality for the DI block. Trip points for this limit switch
functionality are based on the Travel Alert settings in the transducer Block. The DI function block provides the same
type of position detection as the travel alerts in the transducer block. Table 4‐78 lists the transducer block parameters
used with DI block channels 26 through 29. Refer to Travel and Prox, on page 74 for more information on the
transducer block travel alerts.
0= Not Active, 1= Active
Table 4‐78. Transducer Block Parameters Used with Discrete Input Function Block Channels 26 through 29
(Variable Limit Switch)
Transducer Block Parameter
Travel Lo Lo Alert Point
Travel Lo Lo Alert Deadband
Travel Lo Alert Point
Travel Lo Alert Deadband
Travel Hi Alert Point
Travel Hi Alert Deadband
Travel Hi Hi Alert Point
Travel Hi Hi Alert Deadband
Valve Position Proximity Detection
Channels 30 through 33 provide valve position proximity detection for the DI block. The transducer block Travel Alert
Point and Travel Alert Deadband parameters are also used with the valve position proximity, but they provide a
different function. The Travel Alert Point for the selected channel determines the center point for the position to be
detected. The Travel Alert Deadband for the selected channel sets the upper and lower trigger points, or the width of
the proximity detection band. A 1% deadzone exists above and below this band that the travel must exceed to clear
(1)
Transducer Block Index Number
Lo Lo Limit Switch Trip Point
Lo Lo Limit Switch Deadband
Lo Limit Switch Trip Point
Lo Limit Switch Deadband
Hi Limit Switch Trip Point
Hi Limit Switch Deadband
Hi Hi Limit Switch Trip Point
Hi Hi Limit Switch Deadband
Detailed Setup—DI Function Block
33
74.5
0: Travel Open
74.5
1: Travel Closed
74.4
2: Travel Limit Lo Lo
74.4
4: Travel Limit Lo
74.4
3: Travel Limit Hi
74.4
1: Travel Limit Hi Hi
74.5
5: Proximity Lo Lo
74.5
4: Proximity Lo
74.5
3: Proximity Hi
74.5
2: Proximity Hi Hi