Fisher FIELDVUE DVC6200f Instruction Manual page 103

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
PD Detail 1 Active
PD_DETAIL1_ACTIVE
PD Detail 2 Active
PD_DETAIL2_ACTIVE
PD Detail 3 Active
PD_DETAIL3_ACTIVE
PD Detail 4 Active
PD_DETAIL4_ACTIVE
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
Index
RO /
Mode
Number
RW
0: I/P Primary Plugged
1: I/P Nozzle Plugged
2: I/P Latched
3: Reserved
4: Relay Jammed
5: Relay Cross Misadj
6: Relay Bias Diaph Leak
7: Relay Port A Diaph
Leak
8: Relay Port B Diaph
Leak
9: Reserved
(1)
10: Valve Stuck Low or
74.9
RO
ALL
Sensor Arm Damage
11: Valve Stuck High or
Sensor Arm Damage
12: Piston Ring Leak
13: Reserved
14: Low Supply Pressure
15: External Leak
16: SOV Trip
17: Air Line Blocked
18: Reserved
19: Reserved
20: Unknown
(1)
74.10
RO
ALL
Reserved
0: I/P Primary Plugging
1: I/P Nozzle Plugging
2: I/P Calibration Shift
3: Reserved
4: Relay Cross Misadj
5: Relay Port A Diaph
Leak
6: Relay Port B Diaph
Leak
7: Reserved
8: Piston Ring Leak
(1)
74.11
RO
ALL
9: Reserved
10: Reserved
11: Low Supply Pressure
12: Reserved
13: External Leak
14: Reserved
15: Travel Calibration
Shift
16: Unknown
17: Reserved
18: Reserved
(1)
74.12
RO
ALL
Reserved
Range
Initial Value
All bits:0
All bits: 0
All bits: 0
All bits: 0
-Continued-
Detailed Setup—Transducer Block
Protect
Description
Category
Data Type: Bit String (4 byte)
0=inactive
1=active
N/A
Performance Diagnostic Critical
possible cause.
Data Type: Bit String (4 byte)
0=inactive
N/A
1=active
Performance Diagnostic Detail
status.
Data Type: Bit String (4 byte)
0=inactive
1=active
N/A
Performance Diagnostic Reduce
possible cause.
Data Type: Bit String (4 byte)
0=inactive
N/A
1=active
Performance Diagnostic Detail
status
July 2013
101