Fisher FIELDVUE DVC6200f Instruction Manual page 104

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Detailed Setup—Transducer Block
July 2013
Table 4‐14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
PD Detail 5 Active
PD_DETAIL5_ACTIVE
PD Detail 6 Active
PD_DETAIL6_ACTIVE
Shutdown Alerts
SHUTDOWN_ALERTS_ACTIVE
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
102
Index
RO /
Mode
Number
RW
0: Relay Disengaged
1: Insufficient Pressure
Differential
2: Travel Calibration Error
3: Reserved
4: High Supply Pressure*
5: Reserved
6: Near a Travel Cutoff Or
Stop
7:Reserved
(1)
74.13
RO
ALL
8: Spec Sheet Fields
Incomplete*
9: Sensor Failure*
10: Pressure Control
Active
11: Transducer Block
Mode OOS
12: Not Authorized for PD
13: PD Run Disabled*
14: Trigger Data
Available*
(1)
74.14
RO
ALL
Reserved
0: Drive Current
1: Program Memory
2: Static Memory
3: Processor or I/O
Processor
74.15
RO
N/A
4: Travel Sensor
5: Port A Pressure Sensor
6: Output Block Timeout
7-31: (Reserved)
Range
Initial Value
All bits: 0
All bits: 0
All bits: 0
-Continued-
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Bit String (4 byte)
0=inactive
1=active
Performance Diagnostic Detail
N/A
status
*Bits which, when set, will trigger
PERF_ACTIVE bit 2.
Data Type: Bit String (4 byte)
0=inactive
1=active
N/A
Performance Diagnostic Detail
status
Data Type: Bit String (4 byte)
0=inactive
1=active
Indicates what caused an Instrument
Shutdown. Bit remains set even if
N/A
condition has passed if Shutdown
Recovery is Manual. All bits are
cleared when MODE_BLK.TARGET is
written. Always enabled whenever
the corresponding
SHUTDOWN_TRIGGER is enabled.