Remote Travel Sensor Connections - Fisher FIELDVUE DVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Installation
July 2013
e. The instrument is not polarity sensitive. Refer to figure 2‐24. Connect the blue wire to one of the LOOP terminals
in the terminal box. Connect the brown wire to the other LOOP terminal. Cut the green/yellow wire off inside of
the DVC6200f, and ensure that the shield is totally isolated at the instrument end.
Note
The green/yellow wire is cut off inside the DVC6200f to help prevent ground loop issues. The only wires that should be installed
and left on the connector are the two signal wires.
f. Replace the terminal box cap on the terminal box. To secure the terminal box cap engage the lock screw.
3. Connect the field wiring connector to the installed quick connector.

Remote Travel Sensor Connections

The DVC6205f base unit is designed to receive travel information via the Emerson Process Management supplied
DVC6215 feedback unit.
WARNING
Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit
with the remote feedback unit shares a conduit with any other power or signal wiring.
Do not place feedback wiring in the same conduit as other power or signal wiring.
Note
4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection
between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator has been tested to 15
meters (50 feet) maximum without performance degradation.
1. On the feedback unit, remove the housing cap.
2. On the base unit, remove the feedback connections terminal box cap (see figure 2‐21).
3. Install conduit between the feedback unit and the base unit following applicable local and national electrical codes.
Route the 4‐conductor shielded cable between the two units (refer to figure 2‐26).
4. Connect one wire of the 4‐conductor shielded cable between terminal 1 on the feedback unit and terminal 1 on the
base unit.
5. Connect the second wire of the 4‐conductor shielded cable between terminal 2 on the feedback unit and terminal 2
on the base unit.
6. Connect the third wire of the 4‐conductor shielded cable between terminal 3 on the feedback unit and terminal 3
on the base unit.
7. Connect the fourth wire of the 4‐conductor shielded cable between terminal 4 on the feedback unit and terminal 4
on the base unit.
34
Instruction Manual
D103412X012