Detailed Setup—Resource Block
July 2013
D Write Priority
Write Priority (WRITE_PRI [39]) sets the priority for Write Alarm. The lowest priority is 0. The highest is 15.
Communication Time Out
RB > Configure/Setup > Communication Time Out
Field Communicator
D Shed Remote Cascade
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your "advanced" control.
Default value for RCas Timeout is 20 seconds.
Shed Remote Cascade (SHED_RCAS [26]) determines how long function blocks in the DVC6200f should wait before
giving up on remote computer writes to RCas parameters. When the timeout is exceeded, the block sheds to the next
mode as defined by the block shed options. If Shed Remote Cascade is set to 0, the block will not shed from RCas.
Enter a positive value in the Shed Remote Cascade field. Time duration is in 1/32 milliseconds (640000
D Shed Remote Out
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your "advanced" control.
Default value for Shed Remote Out is 20 seconds.
Shed Remote Out (SHED_ROUT [27]) determine how long function blocks in the DVC6200f should wait before giving
up on computer writes to ROut parameters. When the timeout is exceeded, the block sheds to the next mode as
defined by the block shed options. If Shed Remote Out is set to 0, the block will not shed from ROut. Enter a positive
value in the Shed Remote Out field. Time duration is in 1/32 milliseconds (640000
Options
RB > Configure/Setup > Options
Field Communicator
D Diagnostic Options
Diagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the instrument.
D Function Block Options
Function Block Options (FB_OPTIONS [44]) shows which function blocks are available in the instrument.
46