16.2.1

V70 parameters on BOP

The table below lists the parameters displayed on the drive BOP only.
Par. No.
Name
r0020
Speed setpoint smoothed
Description: Displays the currently smoothed speed setpoint at the input of the speed controller or U/f
characteristic (after the interpolator).
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0021
Actual speed smoothed
Description: Displays the smoothed actual value of the motor speed.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0026
DC link voltage smoothed
Description: Displays the smoothed actual value of the DC link voltage.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0027
Absolute actual current
smoothed
Description: Displays the smoothed absolute actual current value.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
Dependency: r0068
r0029
Current actual value field-
generating smoothed
Description: Displays the smoothed field-generating actual current.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0030
Current actual value torque-
generating smoothed
Description: Displays the smoothed torque-generating actual current.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0031
Actual torque smoothed
Description: Displays the smoothed torque actual value.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0032
Active power actual value
smoothed
Description: Displays the smoothed actual value of the active power.
Significance for the drive: Power output at the motor shaft
r0033
Torque utilization smoothed -
Description: Displays the smoothed torque utilization as a percentage.
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0037[0...19]
Servo drive temperatures
418
Min
Max
Factory
setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Unit
Data type
Effective
rpm
Float
-
rpm
Float
-
V
Float
-
Arms
Float
-
Arms
Float
-
Arms
Float
-
Nm
Float
-
kW
Float
-
%
Float
-
°C
Float
-
Commissioning Manual
Can be
changed
-
-
-
-
-
-
-
-
-
-
01/2017