Operation Manual – PoE
H3C S9500 Series Routing Switches

2.3 Displaying PoE Supervision Information

Display the basic
information about the PoE
PSUs.
Display detailed alarm
information about the PoE
PSUs.
Display the number and
current state of AC power
distribution switches of
the PSUs.
2.4 PoE PSU Configuration Example

2.4.1 AC Input Alarm Thresholds Configuration Example

I. Network requirements
Set the overvoltage alarm threshold of AC input for PoE PSUs to 264.0 V.
Set the undervoltage alarm threshold of AC input for PoE PSUs to 181.0 V.
II. Configuration procedure
# Enter system view.
<H3C> system-view
# Set the overvoltage alarm threshold of AC input for PoE PSUs to 264.0 V.
[H3C] poe-power input-thresh upper 264.0
# Set the undervoltage alarm threshold of AC input for PoE PSUs to 181.0 V.
[H3C] poe-power input-thresh lower 181.0
# Display the information about the AC input for the PoE PSUs.
[H3C] display poe-power ac-input state

2.4.2 DC Output Alarm Thresholds Configuration Example

I. Network requirements
Set the overvoltage alarm threshold of DC output for the PoE PSUs to 57.0 V.
Set the undervoltage alarm threshold of DC output for the PoE PSUs to 45.0 V.
II. Configuration procedure
# Enter system view.
To do...
display
supervision-module
information
display poe-power
alarm
display poe-power
switch state
Chapter 2 PoE PSU Supervision Configuration
Use the command...
2-3
Remarks
Available in any view
Available in any view
Available in any view