System Makeup/Function Description - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Building Technologies Division
Infrastructure & Cities Sector
2

System makeup/function description

The LME7... is a microprocessor-based burner control with matching system
components for the control and supervision of forced draft burners of medium to high
capacity.
LME7... are used for the startup and supervision of 1- or 2-stage forced draft burners in
intermittent operation. The flame is supervised with an ionization probe, optionally with
flame detector QRA2..., QRA4.U or QRA10....
Gas burner controls to EN 298 : 2003
-
Oil burner controls to EN 230 : 2005
-
For forced draft gas burners to EN 676
-
For forced draft oil burners to EN 267
-
Integrated in the LME7... basic unit are:
Burner control
BCI for connection a display or PC
Only LME72.../LME73...: Control for one actuator
Lockout reset button (info button)
3 multicolor signal lamp LED for operations and fault notifications
Optional: Analog inputs for load controller DC 0...10 V, DC 0/4...20 mA, 0...135 Ω
3 x 7-segment display for service, fault and operating state information
Interface for program module
Figure 2: Example: Modulating gas burner
Basic Documentation LME7...
2 System makeup/function description
21/245
CC1P7105en
29.11.2011