Function Module Azx61.1; Sequence Control (Signal Adaptation) - Siemens Acvatix SAX61 MO Series Basic Documentation

Table of Contents

Advertisement

DIL switches
DIL switches
HEX switches
Notes
54 / 87
Siemens
Smart Infrastructure
4.3

Function module AZX61.1

Acting direction
1)
OFF
Direct acting positioning signal Y or Z
1)
ON
Reverse acting positioning signal Y or Z
1)
Factory setting: All switches set to OFF
The function module may not be used in combination with SA..61../MO.
4.3.1

Sequence control (signal adaptation)

Sequence control
1)
ON
Sequence control (signal adaptation)
1)
Factory setting: All switches set to OFF
Nr.: 1
· Can only be used with voltage input.
· Maximum input voltage is DC 30 V. If the configuration is invalid, the actuator
operates on DC 0...10 V.
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
Setting sequence control
Rotary switches LO and UP are used to set the starting point or
working range of a sequence.
Position
Starting point
"LO"
0
0,3 V
1
1 V
2
2 V
3
3 V
4
4 V
5
5 V
6
6 V
7
7 V
8
8 V
9
9 V
A
10 V
B
11 V
C
12 V
D
13 V
E
14 V
F
15 V
Invalid HEX switches combinations
LO
0
1 2 3
4
5
6
UP
F F F F F
F
UP
E
UP
UP
UP
Sequence control
Sequence control not active
Sequence control
(signal adaptation)
Position
Working range
"UP"
0
9,4 V
1
3 V
2
4 V
3
5 V
4
6 V
5
7 V
6
8 V
7
9 V
8
10 V
9
12 V
A
14 V
B
16 V
C
18 V
D
20 V
E
25 V
F
30 V
7
8
9
A
B
C
D
E F
F
F
F
F
D D
C
C B
E
E
E
E
E
E
D
D C
F
F
E
E D
F
F E
CE1P4040en
2020-01-30
F

Advertisement

Table of Contents
loading

Table of Contents