General technical data

10.4 Mechanical and climatic environmental conditions

10.4
Mechanical and climatic environmental conditions
Climatic environmental conditions
The following climatic environmental conditions apply (indoor use only):
Environmental requirements
Temperature
Temperature change
Relative humidity
Barometric pressure
Concentration of pollutants
* The FESTO CPV10 and CPV14 valve terminals deviate from the specified operating temperature
range of 0 to 55° C. For the temperature operating range of FESTO valve terminals, refer to the
corresponding FESTO Operating Manuals.
244
Areas of application
0° C to 55° C *
10 K/h
5% to 100%
1080 hPa to 795 hPa
SO
: <0.5 ppm;
2
RH < 60 %, no condensation
H
S: <0.1 ppm;
2
RH < 60 %, no condensation
Operating Instructions, 03/2013, A5E00335544-08
Remarks
All mounting positions
-
with condensation
Corresponds to an altitude of -
1000 m to 2000 m
-
ET 200pro distributed I/O system