Analog electronic modules
15.7 Parameter overview for analog electronic modules
Parameters for 4 AI TC High Feature analog input modules
Group diagnostics
Temperature unit
Interference frequency
suppression
Reference temperature
Measuring method
Measuring range
Diagnostics:
Overflow/underflow
Smoothing
Reference junction
Only possible if the "Reference junction" parameter is set to "Fixed ref. temp.".
1
In accordance with EN 60584, ASTM E 230, GOST R8.585, JIS C1602; type L according to DIN
2
43710
424
Parameters
Disable
•
Enable
•
Celsius
•
Fahrenheit
•
Kelvin
•
Off
•
10 Hz
•
50 Hz
•
60 Hz
•
See below,
1
Disabled
•
Thermocouple
•
Voltage ±80 mV
•
2
Type B [PtRh-PtRh]
•
Type E [NiCr-CuNi]
•
Type J [Fe-CuNi]
•
Type K [NiCr-Ni]
•
Type L [Fe-CuNi]
•
Type N [NiCrSi-NiSi]
•
Type R [PtRh-Pt]
•
Type S [PtRh-Pt]
•
Type T [Cu-CuNi]
•
Disable
•
Enable
•
None
•
Weak
•
Average
•
Strong
•
None
•
Internal
•
RTD (0)
•
Dynamic ref. temp. (see
•
below)
Fixed ref. temp. (see
•
below)
Value range
Disable
Celsius
50 Hz
"Reference temperature" parameter for 4 AI TC High Feature
Thermocouple
Type K [NiCr-Ni]
Disable
None
Internal
Operating Instructions, 03/2013, A5E00335544-08
Default
Effective range
Module
Module
Module
Channel
Channel
Channel
Channel
Channel
ET 200pro distributed I/O system