Alarm, error and system messages
9.1 PROFIBUS DP
9.1.6

Station states 1 to 3

Definition
Station states 1 to 3 provide an overview of the status of a DP slave.
Structure of station status 1 (byte 0)
Bit
Meaning
0
1: The DP master cannot address the DP slave.
1
1: The DP slave is not yet ready to exchange data.
2
1: The configuration data transferred from the DP
master to the DP slave does not match the DP
slave configuration.
3
1: External diagnostic information exists.
(group diagnosis display)
4
1: The DP slave does not support the requested
function (modification of the PROFIBUS address in
the software, for example).
5
1: The DP master cannot interpret the response of
the DP slave.
6
1: The DP slave type does not match the software
configuration.
7
1: The DP slave was parameterized by a different
DP master (not by the DP master which currently
has access to the DP slave).
200
Cause/remedy
Check the PROFIBUS address of the DP slave.
Check the PROFIBUS DP connection.
Check the power supply to the DP slave.
Check the settings of the RS 485 repeater.
Check whether the DP slave was reset.
Wait, the DP slave is currently starting up.
Verify the station type and configuration of the DP slave in
the configuring software.
Evaluate the ID-specific and/or channel-specific diagnostic
information, and the module status. Bit 3 is reset after all
errors are cleared. The bit will be set again if a new
diagnostic message is output in the bytes of the
diagnostics functions mentioned above.
Check the configuration.
Check the bus configuration.
Compare the preset to the actual configuration
The bit is always 1 if, for example, you are currently
accessing the DP slave from the PG or a different DP
master.
The PROFIBUS address of the DP master which has
parameterized the DP slave is in the "Master PROFIBUS
address" diagnostics byte.