Pin assignment on CM IO 2 x M12 connection module and 4 DI / 4 DO DC 24V/0.5A electronic
module
Table 4- 17
View of circular connector
Pin assignment on the CM IO 1 x M23 connection module and the 4 DO DC 24V/2.0A electronic
module
Table 4- 18
View of circular connector
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
4.11 Wiring the Electronic Module using the Connection Module
Pin assignment on CM IO 2 x M12 connection module and 4 DI / 4 DO DC 24V/0.5A
electronic module
Pin assignment of CM IO 1 x M23 with 4 DO DC 24V/2.0A
Terminal
Assignment X1 and X2
1
Input signal DI
Output signal DQ
2
Input signal DI
Output signal DQ
3
Input signal DI
Output signal DQ
4
Input signal DI
Output signal DQ
5
24 V encoder supply U
(is supplied by the ET 200pro to the
connected encoder): Connector X1
Not assigned: Connector X2
6
Not assigned
7
Ground 2M
8
Functional earth (FE)
Terminal
Assignment X1
1
Output signal DQ
2
Output signal DQ
3
Output signal DQ
4
Output signal DQ
5
Not assigned
6
Not assigned
7
Not assigned
8
Not assigned
9
Ground for load voltage supply 2M
10
Ground for load voltage supply 2M
11
Not assigned
12
Functional earth (FE)
Connection
: Connector X1
0
: Connector X2
0
: Connector X1
1
: Connector X2
1
: Connector X1
2
: Connector X2
2
: Connector X1
3
: Connector X2
3
(from 2L+)
S
0
1
2
3
119