Connection
4.5 Connecting the interface module to a CM IM DP Direct connection module
Opening and preparing the connection module
1. Remove the two screws from the bottom of the connection module using a crosstip
screwdriver.
2. Remove the cover from the connection module.
3. Install M20 screwed cable glands at the cable inlets using an open-end wrench. The blind
plates will break off automatically when you screw in the glands. Tighten the cable glands
on the connection module (torque = 3 Nm).
4. Feed the PROFIBUS Hybrid cable through the bottom cable gland in order to achieve a
maximum possible bending radius.
Stripping PROFIBUS Hybrid cables
1. Strip the PROFIBUS Hybrid over a length of 97 mm.
2. Remove the white filler material, and the two black fillers of the 4-wire PROFIBUS Hybrid
cable.
3. Slide the shielding braid back towards the sheath by approx. 15
4. Carefully strip off the shielding film and the two white fillers from the PROFIBUS DP
cable.
Figure 4-8
82
Stripping dimensions for PROFIBUS Hybrid cables
mm.
+/-2
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08