Advertisement

Connection

4.5 Connecting the interface module to a CM IM DP Direct connection module

4.5
Connecting the interface module to a CM IM DP Direct connection
module
4.5.1

Requirements

Introduction
You connect the power supplies and PROFIBUS DP to the CM IM DP Direct connection
module. You can loop the supply voltages and PROFIBUS DP using the relevant terminals.
● Power supplies 1L+, 2L+: The cables are terminated on screw terminals.
PROFIBUS DP: The bus cables are terminated on insulation displacement terminals (Fast
Connect technology). The insulation displacement terminals are designed to withstand
10 terminating cycles.
Requirements
● The interface module and bus module are mounted on the rack.
● You have set the PROFIBUS DP address on the connection module according to your
configuration.
78
Insulation displacement terminals for PROFIBUS DP
Screw terminals for looping the load voltage supply 2L+
Screw terminals for looping the electronic / encoder supply 1L+
Screw terminals for feeding the electronic / encoder supply 1L+
Screw terminals for feeding the load voltage supply 2L+
Terminating resistor for PROFIBUS DP
DIP switch for setting the PROFIBUS DP address
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08