Description
1.5 Components of the ET 200pro distributed IO system
Component
Connection
modules for
electronic
modules
Pneumatic
interface
modules
28
Function
The connection modules are mounted
on the electronic modules. They are
used to connect sensors and
actuators.
The following connection modules are
available:
8 circular socket connectors:
•
①
CM IO 8 x M12
CM IO 8 x M12P ①
②
CM IO 8 x M12D
④
CM IO 8 x M8
4 circular socket connectors:
•
③
CM IO 4 x M12
CM IO 4 x M12P ③
CM IO 4 x M12 Inverse ③
2 circular socket connectors
•
(for 2 actuator/
sensor distributors):
⑤
CM IO 2 x M12
1 circular socket connector
•
(for 1 actuator/
sensor distributor)
⑥
CM IO 1 x M23
The pneumatic interface modules
allow the linking of FESTO valve
terminals CPV10 and CPV14. Each
of the two FESTO valve terminals can
be equipped with up to 16 valves
(standard components of FESTO).
The valve terminals differ in terms of
nominal flow rate of air (CPV10:
400 l/min; CPV14: 800 l/min).
Following pneumatic interface
modules are available:
16 DO DC 24V CPV10
•
16 DO DC 24V CPV14
•
View
①
②
Operating Instructions, 03/2013, A5E00335544-08
ET 200pro distributed I/O system