Mechanical And Climatic Environmental Conditions - Siemens SIMATIC ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC ET 200eco PN:
Table of Contents

Advertisement

General technical data

8.3 Mechanical and climatic environmental conditions

Emission of radio interference
Interference emission of electromagnetic fields according to EN 55011: Limit class A, group
1 (measured at a distance of 10 m).
Frequency
30 MHz to 230 MHz
230 MHz to 1000 MHz
Shipping and storage conditions
The ET 200eco PN distributed I/O device surpasses the requirements according to
IEC 61131-2 for transport and storage conditions. The following information applies to
modules transported or stored in their original packaging.
Type of condition
Free fall
Temperature
Temperature change
Air pressure
Relative humidity
8.3
Mechanical and climatic environmental conditions
Climatic environmental conditions
Applicable climatic environmental conditions:
Environmental conditions
Temperature
Temperature change
Relative humidity
Air pressure
Pollutant concentration
90
Fields of application
0 to 55°C
10 K/h
5 % to max. 100 %
1080 hPa to 795 hPa
SO
: < 0.5 ppm;
2
relative humidity < 60 %, no dewing
H
S: < 0.1 ppm;
2
relative humidity < 60 %, no dewing
Noise emission
< 40 dB (µV/m)Q
< 47 dB (µV/m)Q
Permissible range
≤ 0.3 m
- 40°C to +70°C
20 K/h
1080 hPa to 660 hPa
(corresponds with an altitude of -1000 m to
3500 m)
5 % to 95 %,
Without condensation
Remarks
All mounting positions
With condensation
Corresponds to an altitude of -1000 m
to 2000 m
Test:
10 ppm; 4 days
1 ppm; 4 days