Power modules
13.1 PM-E power module
Technical specifications
Technical specifications
Dimensions and weight
Dimensions W × H × D (mm)
Weight
Voltages and currents
Rated load voltage
•
•
Max. current carrying capacity (up to 55° C)
•
Current consumption
From load voltage 2L+
Power loss of the module
Electrical isolation
•
•
•
Isolation
Isolation tested with
Status, interrupts, diagnostics
Diagnostic function
•
•
•
322
Overvoltage protection
Reverse polarity protection
Short-circuit protection
Between the rated load voltage 2L+ and the
backplane bus
Between the 1L+ electronics/encoder
supply and the backplane bus
Between
power modules
Group error
Rated load voltage monitoring
Diagnostic information can be read
45 × 130 × 35
Approx. 140 g
24 V DC
No
Yes; against destruction
10 A; on the internal busbars of ET 200pro
Yes; replaceable fuse in the power module
Max. 3 mA
Typ. 0.1 W
Yes
Yes
Yes; if 1M and 2M are not bridged by an external
circuit
500 V DC
Yes
Red "SF" LED
Green "DC 24V" LED
Yes
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08