Commissioning ET 200pro

Introduction
You commission the automation system according to the relevant plant configuration. The
section below describes the procedure of commissioning the ET 200pro connected to an
IO controller.
Requirements of ET 200pro on PROFINET IO
Actions
ET 200pro is mounted
ET 200pro is wired
The SIMATIC Micro Memory Card is inserted
Assigning device names to the I/O device
ET 200pro is configured
Supply voltage to the I/O controller is switched on
I/O controller is in RUN
Commissioning ET 200pro
1. Switch on the electronic / encoder supply 1L+ for ET 200pro.
2. Switch on the load voltage supply/ies 2L+.
See also
Mounting the Interface Module (Page 53)
Configuring by Means of GSD File (Page 148)
Configuring in STEP 7 (Page 147)
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
Note
Changes to the backplane bus
Always switch off/on power to the electronic / encoder supply 1L+ before you modify the
backplane bus configuration (number of modules, removal of the terminating module).
Commissioning
6.2 PROFINET IO