Technical specifications
Technical specifications
Dimensions and weight
Dimensions W x H x D (mm)
Weight
Voltages and currents
Rated load voltage 2L+
•
•
Total current of the outputs
•
•
Current consumption
•
•
Power loss
Digital outputs
Number of digital outputs
Cable length, shielded
Cable length, unshielded
Short-circuit protection of the output
•
Limitation of the inductive cut-off voltage to lamp
load
Lamp load
Control of a digital input
Output voltage
•
•
Output current
•
•
Wiring 2 outputs in parallel
•
•
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
14.6 Digital electronic module 8 DO DC 24V/0.5A (6ES7142-4BF00-0AA0)
Reverse polarity protection
Short-circuit protection
All mounting positions up to 40 °C
All mounting positions up to 55 °C
From backplane bus
From load voltage 2L+ (without load)
Response threshold
Rated value
With "1" signal
With "1" signal
With "0" signal (residual current)
For performance increase
For redundant control of a load
Digital electronic modules
45 x 130 x 35; with bus module, without
connection module
Approx. 140 g
24 V DC
Yes; against destruction; loads will be activated
Yes; per channel
4 A
4 A
< 30 mA
< 30 mA
Typ. 2 W
8
Max. 30 m
Max. 30 m
Yes, electronic, per channel
Min. 0.7 A
Typ. 2L+ (-47 V)
Max. 5 W
Yes; no electrical isolation between 1L+ and 2L+,
because 1M and 2M are jumpered
24 V DC
Min. 2L+ (-0.8 V)
0.5 A
Max. 0.5 mA
No
Supported
359