Omron NT - SUPPORT TOOL FOR WINDOWS V4 Operation Manual page 489

Table of Contents

Advertisement

Data Conversion
Correction related the number of digits for numeral display
Correction related to analogue meter
Correction related to control touch switch of trend graph
480
In the conversion of the data between a conventional and a new model, conver-
sion is executed in the manner shown below due to differences in the range of
numeric values that can be displayed.
S Difference
New models:
Conventional models:
S Conversion result, error message and corrective action
Status before
Conversion
With a new model,
With a conventional
a numeral display
model, a numeral
element for which a
display element of
numeric value ex-
greater than 8 digits
ceeding 8 digits is
is discarded.
displayed is regis-
tered to the symbol
manager.
In the conversion of the data between new models (with "-V1" and above) and
other PT models, conversion is executed in the manner shown below due to
presence/absence of analogue meter.
S Difference
New models (with "-V1" and above):
Conventional models, new models (below "-V1"):
S Conversion result, error message and corrective action
Status before
Conversion
With a new model
With a conventional
("-V1" and above),
model and a new
an analogue meter
model (below
is registered to the
"-V1"), an analogue
symbol manager.
meter is not dis-
played.
In the conversion of the data between a conventional and a new model, conver-
sion is executed in the manner shown below due to differences in the trend graph
control touch switches.
S Difference
New models:
Conventional models:
A numeric value of up to 10 digits can be displayed.
A numeric value of up to 8 digits can be displayed.
Status after
Error Message
Conversion
Numeral Display:
Total number of in-
teger and decimal
exceeds limit. It is
discarded.
Analogue meter can be used.
Analogue meter cannot be used.
Status after
Error Message
Conversion
Cannot paste ana-
logue meter. It is
discarded.
Marks with codes FFEF to FFF5 (hexadecimal) are
used as trend graph control touch switches.
No trend graph control touch switches (codes FFEF
to FFF5 may be used as desired).
Appendix A
Corrective Action
Create a new numeral
display element. Correct
the screen data or the
program at the host so
that a constant of up to
8 digits suffices. (Refer
to 6-6 Numeral Display.)
Corrective Action
Create a bar graph or
other display element
instead of an analogue
meter to display con-
tents that was displayed
by an analogue meter.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt-series support tool for windows 4

Table of Contents