Common Operation
130
Character
Area Type
D
Data Register
R
File Register
W
Link Register
f
: Specification possible
Input a word address as a 4-digit number (leading zeros can be suppressed) and
a bit number as a 2-digit number.
PLC Vendor: Mitsubishi_Fx
Possible areas and characters that indicate area types are as follows:
Character
Area Type
X
Input Relay
Y
Output Relay
M
Auxiliary Relay
S
State
C
Counter
T
Timer
D
Data Register
f
: Specification possible
Input a word address as a 4-digit number (leading zeros can be suppressed) and
a bit number as a 2-digit number.
PLC Vendor: AB
Possible file types and characters are as follows (available only for NT31/631
models):
Character
File Type
B
Bit
C
Counter
N
Integer
R
Control
S
Status
T
Timer
Character
File Type
I
Input
O
Output
f
: Specification possible
Input a file number as a 3-digit number (leading zeros can be suppressed), ele-
ment number or word address as 3-digit number, sub-element number as 1 digit
and bit number as a 2-digit number.
PLC Vendor: GE
Word
f
f
f
: Specification not possible
Word
f
f
f
f
f
f
f
: Specification not possible
File/Slot
Element/
Number
Word
Number
f
f
f
f
f
f
f
f
f
f
Slot Number
Address
f
f
f
f
: Specification not possible
Section
6-1
Bit
f
f
f
Bit
f
f
f
f
f
Sub-Ele-
Bit/Termi-
ment
nal Num-
Number
ber
f
f
f
f
f
f
f
f
f
Word
Bit/Terminal
Number
f
f