Connecting Cables and Terminating Resistor
Flat Cable I
Installation Method
Flat Cable II
Installation Method
70
Flat Connector Socket
Trunk line or sub-trunk line
Flat Connector Plug
Up to 10 sets of
Connectors can be used.
Attach a DCN4-BR4 Flat Connector Plug to a DCN4-TR4 Flat Connector
Socket connected to Communications Cable.
Flat Connector Plug
Flat Connector Socket
Be sure the surface of the Flat Connector Plug on which line colors are indi-
cated (red, white, black, and blue) is facing downward and press in the Con-
nector until it clicks into place.
Note To remove a Connector once it has been attached, press in on the
latches on both sides of the Connector and pull it out.
Attach a DCN5-BR4 Flat Connector Plug to a DCN5-TR4 Flat Connector
Socket connected to Communications Cable.
Flat Connector Plug
Flat Connector Socket
Orient the Flat Connector Plug so that the white line on the cable is facing
downward and press in the Connector until it clicks into place.
Note To remove a Connector once it has been attached, press in firmly
on the latches on both sides of the Connector and pull it out.
Flat Connector Socket
Trunk Line or
Sub-trunk Line
Flat Connector Plug
Section 3-4
Terminating Resistor