Omron CRT1 - 10-2008 Operation Manual page 303

Componet slave units and repeater unit
Table of Contents

Advertisement

Units with Clamp Terminal Blocks
Output Section Specifications
Model
I/O capacity
Internal I/O common
Rated output current
Residual voltage
Leakage current
ON delay
OFF delay
Number of circuits per common
Isolation method
Output indicators
Power supply type
Current supplied to output devices
I/O power supply current consumption
Output handling for communications
errors
Component Names and Functions (Same for CRT1-MD16SL and CRT1-MD16SL-1)
Communications
indicators: MS and NS
Indicator Section
Communications
Indicators
I/O Indicators
280
Item
Node address switches:
×10 and ×1 (from left)
I/O indicators
Communications
Connector
Screw-less clamp terminal
Refer to 4-1-3 Communications Indicators.
The meanings of the output indicators are given in the following table.
Name
0 to 7 (inputs)
Lit yellow.
0 to 7 (outputs)
Not lit.
Specification
CRT1-MD16SL
8 outputs
NPN
0.5 A/output, 2 A/common
1.2 V max. (0.5 A DC, between
each output terminal and the G
terminal)
0.1 mA max.
0.5 ms max.
1.5 ms max.
8 outputs/common
Photocoupler
LED (yellow)
Multi-power supply
100 mA/output
25 mA max. for 24-VDC power supply voltage
Select either hold or clear from CX-Integrator.
Input indicators
I/O power
0 to 7
supply indicator
Release button
LED status
I/O status
Input or output
ON
Input or output
OFF
Section 5-5
CRT1-MD16SL-1
PNP
1.2 V max. (0.5 A DC, between
each output terminal and the V
terminal)
Output indicators
0 to 7
I/O power supply indicator
Meaning
The input or output is
ON.
The input or output is
OFF.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crt1 series

Table of Contents