Omron CRT1 - 10-2008 Operation Manual page 493

Componet slave units and repeater unit
Table of Contents

Advertisement

Temperature Input Unit Functions
470
2. Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select Parameter - Edit.
The Configuration Window will be displayed.
3. Click the tab for the input where time is to be measured, and select the
Comparator Check Box in the Function Choice Area.
4. Click the Comparator Tab and select the desired type of temperature
range in the Zone Type Field.
5. Set the monitor value in the Monitoring Zone Counter Field to indicate
when the temperature has been in the temperature range longer than the
set value.
Section 11-5