Omron CRT1 - 10-2008 Operation Manual page 479

Componet slave units and repeater unit
Table of Contents

Advertisement

Temperature Input Unit Functions
456
3. Click the tab for the input where scaling is to be performed, and select the
Scaling Check Box in the Function Choice Area.
4. Set 0% value in the Scaling Point (0%) Field, and set the 100% value in the
Scaling Point (100%) Field.
5. To offset the scaled values, set the offset value in the Scaling Offset Field.
Section 11-5