Analog Input Slave Units
Note
Setting the Input
Range from the CX-
Integrator
1,2,3...
■ Inputs 2 and 3 (Shared Setting)
Input range
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
When the DIP switch is used to set the input ranges (pin 8 ON), the input sig-
nal ranges must always be the same for Inputs 0 and 1 and for Inputs 2 and 3.
If it is necessary to set separate input signal ranges for Inputs 0 to 3, use the
CX-Integrator rather than the DIP switch to make the settings.
Use the following procedure to set the input range for each input using the
CX-Integrator.
1. Turn ON the power to the CompoNet Slave Unit.
2. Double-click the icon of the Slave to be set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
Slave Unit icon and select Parameters - Edit from the menus.)
3. Select the Tab Page for the input where the range is to be changed.
4. Select the desired range from the pull-down menu in the Input Range Field.
5. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
download the data, and then click the Reset Button to reset the Unit.
6. Click the OK Button and exit the window.
Pin 4
Pin 5
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Section 6-4
Pin 6
OFF
OFF
OFF
OFF
ON
ON
299