Analog I/O Slave Unit Functions
Cumulative Counter
Note
Setting Using the CX-Integrator
1,2,3...
To return the set value to the default setting, click the Default Setting But-
ton.
8. Click the Close Button to close the Adjustment Window.
9. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
download the data, and then click the Reset Button to reset the Unit.
10. Click the OK Button and exit the window.
The cumulative counter calculates an approximation to the integral of analog
input values over time. The cumulated value can be calculated in "count
hours" (by selecting "hours") or "count minutes" (by selecting "minutes"). The
count value is the analog input value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
input value of 100 counts continuing for one hour. The counter range for a
four-byte area (two words) for count hours or count minutes is –214,748,364.8
to 214,748,364.7. Data is displayed on the CX-Integrator in units of 0.1 hour
or minute.
Monitor values can be set in the Slave Unit. When the cumulated count value
exceeds the set monitor value, the Cumulative Counter Flag in the area for
Generic Status Flags turns ON.
Analog input value
Division width (See note.)
The following table shows the divisions for the cumulative counter.
Unit
Hour
3.6 s (1/1,000 hour)
Minute
60 ms (1/1,000 minute)
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
3. Select the Tab Page for the input where the cumulative counter is to be set,
and select Cumulated Count under the Function Choice heading.
Cumulated value
(count × hour or count × minute)
Time
Divisions
Section 11-4