Temperature Input Units
Node Address
Settings
Setting the Input Type
Setting with the DIP
Switch
The node address of the Temperature Input Unit is set as a decimal value
using the left rotary switch for the ten's digit and the right rotary switch for the
one's digit. (Up to 63 nodes can be set.)
Note The rotary switch settings are read when the power is turned ON.
0
0
The input type can be set using the DIP switch or the CX-Integrator.
1
2
3
4
5
6
Set each pin according to the following table.
Pin No.
SW1
Sets the input type (input
range)
SW2
SW3
SW4
SW5
Always OFF
SW6
Selects °C or °F display.
SW7
Always OFF
SW8
Selects the input type set-
ting method.
CRT1-TS04T
SW1
SW2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Node address, x1
Node address, x10
7
8
Setting
Refer to the following table.
Default setting: All pins OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
OFF: °C conversion
ON: °F conversion
Default setting: OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
OFF: Set with CX-Integrator.
ON: Set with DIP switch.
Note When the input type is set with the DIP
switch, all inputs are set to the same
input type.To set different input types,
use the CX-Integrator to make the set-
tings.
SW3
SW4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
Section 7-5
Specifications
Input type
R
S
K (−200 to 1300°C)
K (0.0 to 500.0°C)
J (−100 to 850°C)
J (0.0 to 400.0°C)
T
E
L (−100 to 850°C)
L (0.0 to 400.0°C)
337