Omron CRT1 - 10-2008 Operation Manual page 335

Componet slave units and repeater unit
Table of Contents

Advertisement

Analog Output Slave Units
Setting Using the CX-
Integrator
1,2,3...
312
■ Output 0 Range
Signal range
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
■ Output 1 Range
Signal range
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
Use the following procedure to set the output range for each output using the
CX-Integrator.
1. Turn ON the power to the CompoNet Slave Unit.
2. Double-click the icon of the Analog Output Unit to set in the Network Con-
figuration Window to open the Configuration Window. (Alternatively, right-
click the icon and select Parameters - Edit from the pop-up menu.)
3. Select the Tab Page for the output where the range is to be changed.
4. Click the Output Range Field, and select the desired range.
5. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
download the data, and then click the Reset Button to reset the Unit.
6. Click the OK Button and exit the window.
Pin 1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Pin 4
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Section 6-5
Pin 2
Pin 3
OFF
OFF
OFF
OFF
ON
ON
Pin 5
Pin 6
OFF
OFF
OFF
OFF
ON
ON

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crt1 series

Table of Contents