Omron CRT1 - 10-2008 Operation Manual page 440

Componet slave units and repeater unit
Table of Contents

Advertisement

Word Slave Unit and Bit Slave Unit Functions
Settings Using the CX-Integrator
1,2,3...
Measured approx. every 1 s
ON
OFF
1.5 s
Figure C
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
3. Click the IN Tab.
4. Double-click the I/O Comment column for the terminal to be set. The Edit
Terminal Window will be displayed. Select Time for the Detection Mode,
enter the monitor value in the Value Field, and then click the OK Button.
5. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
download the data, and then click the Reset Button to reset the Unit.
6. Click the OK Button and exit the window.
Section 11-3
417