Analog I/O Slave Unit Functions
5. When User Scaling is selected, set the 0% value in the Scaling Point (0%)
Field, and set the 100% value in the Scaling Point (100%) Field.
6. For offset compensation, set the offset value in the Scaling Offset Field.
Either Default Scaling or User Scaling can be set in the Scaling Type Field.
7. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
download the data, and then click the Reset Button to reset the Unit.
8. Click the OK Button and exit the window.
Section 11-4