Omron CRT1 - 10-2008 Operation Manual page 541

Componet slave units and repeater unit
Table of Contents

Advertisement

CompoNet Explicit Messages
Setting and Reading for Analog Output Units
Explicit
Read
message
/write
Analog Out-
Read Reads analog output
put Value
values.
Read
Output
Write/
Sets the output range.
Range Set-
Read
4 to 20 mA: 0;
ting
0 to 10 V: 1;
0 to 20 mA: 2;
−10 to 10 V: 3;
0 to 5 V: 4;
1 to 5 V: 6
Communi-
Write/
Sets the communica-
cations
Read
tions error output value
Error Out-
for each output.
put Setting
0: Hold last state
1: Low limit
2: High limit
3: Zero count
Function
Write/
Sets the function.
Setting
Read
Scaling: 0;
Cumulative counter: 1
Scaling
Write/
Default scaling: 0:
Type Set-
Read
User scaling: 1
ting
Scaling
Write/
Sets a conversion value
Point 1 Set-
Read
as the 0% value for user
ting
scaling.
Scaling
Write/
Sets a conversion value
Point 2 Set-
Read
as the 100% value for
ting
user scaling.
Offset
Write/
Compensates for scal-
Compensa-
Read
ing errors with an offset
tion after
value.
Scaling
Cumulated
Read/
Reads the cumulated
Value Read
Reset
analog output value.
Cumulative
Read Reads the cumulative
Counter
count status in the
Flag Read
Cumulative Counter
Flag in the area for
Generic Status Flags.
0: Counter overflow
1: Counter underflow
7: Set value overflow
518
Function
Service
code
0E hex
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Read:
0E hex
Reset:
35 hex
Read:
0E hex
Command
Class
Instance
Command data
ID
ID
Attribute
ID
0B hex 01 to 02
03 hex
hex
0B hex 01 to 02
07 hex
hex
0B hex 01 to 02
09 hex
hex
0B hex 01 to 02
6E hex
hex
0B hex 01 to 02
6F hex
hex
0B hex 01 to 02
70 hex
hex
0B hex 01 to 02
71 hex
hex
0B hex 01 to 02
72 hex
hex
0B hex 01 to 02
91 hex
hex
0B hex 01 to 02
92 hex
hex
Appendix A
Response
Service data
Data
---
2 bytes
---
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
---
2 bytes
2 bytes
(−28000 to
(−28000 to
28000)
28000)
2 bytes
2 bytes
(−28000 to
(−28000 to
28000)
28000)
2 bytes
2 bytes
(−28000 to
(−28000 to
28000)
28000)
---
4 bytes
(−214748364.8
to
214748364.8)
---
1 byte