Omron CRT1 - 10-2008 Operation Manual page 408

Componet slave units and repeater unit
Table of Contents

Advertisement

Clamp Terminal Blocks
Output Section Specifications
Model
I/O capacity
Internal I/O common
Rated output current
Load power supply voltage
Residual voltage
Leakage current
ON delay
OFF delay
Number of circuits per com-
mon
Load power short-circuit
detection
Isolation method
Input indicators
Component Names and Functions (Same for CRT1B-MD04SLP/CRT1B-MD04SLP-1)
Communications indicators: MS and NS
Display Section
Communications
Indicators
Item
2 outputs
NPN
0.2 A/output
Communications power supply voltage + 0 V (max.)
Communications power supply voltage − 1.2 V (min.)
1.2 V max. (0.2 A DC, between each
output terminal and BS−)
0.1 mA max.
0.5 ms max.
1.5 ms max.
2 outputs/common
Supported.
No isolation
LEDs (yellow)
Power short-circuit indicators (SHT0 and SHT1)
Refer to 4-1-3 Communications Indicators.
Specification
CRT1B-MD04SLP
Node address switches:
×100, ×10, and ×1
I/O indicators 0 and 3
Flat Cable
(attached)
Section 9-4
CRT1B-MD04SLP-1
PNP
1.2 V max. (0.2 A DC, between each
output terminal and BS+)
I/O connectors
(screwless clamp terminals)