Analog I/O Slave Unit Functions
Setting Using the CX-Integrator
1,2,3...
Moving Average
Processing
Setting Using the CX-Integrator
1,2,3...
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
3. Click the General Tab and select the number of conversion points from the
inputs listed on the pull-down menu under the Available Channels Field.
4. Click the Transfer [PC to Unit] Button to download the data, and then click
the Reset Button to reset the Unit.
5. Click the OK Button and exit the window.
This function calculates the average value (moving average) of the previous
eight inputs, and uses the resulting value as conversion data. When the input
value fluctuates frequently, as shown in the following diagram, averaging can
be used to produce a stable input value.
Input analog value
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
Section 11-4
Actual input
Averaged input
Time
421