Omron CRT1 - 10-2008 Operation Manual page 506

Componet slave units and repeater unit
Table of Contents

Advertisement

Temperature Input Unit Functions
1,2,3...
Note
1,2,3...
Checking That the Adjustment Is Effective
1. Right-click the Unit icon to be adjusted and select Monitor. The Monitor
Window will be displayed.
2. Click the tab for the temperature input that was adjusted. If the User Ad-
justment Check Box is selected, the Unit is operating with user-set adjust-
ment values.
(1) When checking whether the user adjustment values have been set cor-
rectly, refresh the data by clicking the Update Button in the Monitor Win-
dow's General Tab Page or uploading the settings again. For details on
the Monitor Window, refer to 7-4 Monitoring Temperature Data.
(2) If the correct reference voltage was not input, the adjustment values may
not be accepted.
Adjusting the Bias Compensation Value
1. Disconnect the wiring for adjusting the upper and lower limits and change
to wiring for bias compensation.
2. After completing the wiring, wait at least 20 minutes with the temperature
data in a stable state, and click the Fix Bias Value Button in the Bias Ad-
justment Window. The bias compensation value will be written in the Unit.
Resetting Adjustments
If it is necessary to reset the upper limit adjustment value, lower limit adjust-
ment value, and bias compensation value to the factory defaults, click the
Default Setting Button. The settings will be returned to the factory settings.
The upper/lower limit adjustment values and bias compensation value are all
initialized at the same time.
Section 11-5
483

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crt1 series

Table of Contents