Temperature Input Unit Functions
OFF Delay
Setting Using CX-Integrator
1,2,3...
The time until the Comparator Result Flag turns OFF can be extended. For
example, even if the Flag is ON momentarily, the OFF delay can be set so that
the Master Unit can receive notification of the Flag's status.
HH set value
HH Alarm Flag
1. Turn ON the power supply to the Temperature Input Unit.
2. Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select Parameter - Edit.
The Configuration Window will be displayed.
3. Click the tab for the input where comparator function is to be set, and select
the Comparator Check Box in the Function Choice Area.
4. Click the Comparator Tab and set each of the alarm values. The example
here shows the setting for Alarm Trip Point High (HH).
Hysteresis width
OFF delay
Section 11-5
467