Omron CRT1 - 10-2008 Operation Manual page 577

Componet slave units and repeater unit
Table of Contents

Advertisement

Precautions with Connecting Two-wire DC Sensors
Relation between OFF Current of Slave Unit with DC Inputs and
Sensor Leakage Current
≥ I
I
OFF
leak
I
:
OFF current of a Slave Unit with DC Inputs
OUT
I
:
Sensor's leakage current
leak
Connect a bleeder resistor if the Sensor's leakage current is greater than the OFF current of a Slave Unit with
DC Inputs.
The bleeder resistor constant can be calculated using the following equation.
R ≤ (I
× R
+ V
)/(I
OFF
IN
F
leak
2
Power W ≥ (V
− V
)
CC
R
554
− V
)
OFF
/R × 4 [allowable margin]