Advertisement

Analog Output Slave Units
Output Range: 0 to 5 V
Output Range: 1 to 5 V
Output Range: 0 to 10 V
Output Range:
10 to 10 V
314
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 0 to
5 V. The output range is
Voltage
5.25 V
5 V
0 V
8000FED4 (−300)
−0.25 V
0000 (0)
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 1 to
5 V. The output range is 0.8 to 5.2 V.
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
0000(0)
8000
(−300)
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 0 to
10 V. The output range is
Voltage
10.5 V
10 V
0 V
8000FED4 (−300)
−0.5 V
0000 (0)
The values F448 to 0BB8 hex (
range
10 to 10 V. The output range is
specified as two's complements (16 bits).
0.25 to 5.25 V.
1770
189C
(6000)
(6300)
1770
189C
(6000)
(6300)
0.5 to 10.5 V.
1770
189C
(6000)
(6300)
3,000 to 3,000) correspond to the voltage
11 to 11 V. Negative voltages are
Section 6-5
Conversion data
Hexadecimal
7FFF
(decimal)
Conversion data
Hexadecimal
7FFF
(decimal)
Conversion data
Hexadecimal
7FFF
(decimal)