CompoNet Explicit Messages
Setting and Monitoring the Outputs
Explicit
Read
message
/write
Terminal
Read Reads the monitor mode
Mainte-
for maintenance infor-
nance Infor-
mation of the output (No.
mation
1 to 32) specified by the
Monitor
Instance ID.
Mode
Write Writes the monitor mode
for maintenance infor-
mation of the output (No.
1 to 32) specified by the
Instance ID.
Set Value
Read Reads the set value for
for Output
the total ON time (unit: s)
Total ON
or number of contact
Time or
operations (unit: opera-
Contact
tion) for the output (No. 1
Operation
to 32) specified by the
Counter
Instance ID.
Write Writes the set value for
the total ON time (unit: s)
or number of contact
operations (unit: opera-
tion) for the output (No. 1
to 32) specified by the
Instance ID.
Output
Read Reads the total ON time
Total ON
(unit: s) or number of
Time or
contact operations (unit:
Contact
operation) for the output
Operation
(No. 1 to 32) specified by
Counter
the Instance ID.
Read
Reset for
Reset Resets the total ON time
Output
(unit: s) or number of
Total ON
contact operations (unit:
Time or
operation) for the output
Contact
(No. 1 to 32) specified by
Operation
the Instance ID to 0.
Counter
Reset
Monitor
Read Reads the monitor sta-
Status for
tus for total ON time or
Output
contact operation
Total ON
counter for the output
Time or
(No. 1 to 32) specified by
Contact
the Instance ID.
Operation
Counter
Read
508
Function
Service
code
0E hex
10 hex
0E hex
10 hex
0E hex
05 hex
0E hex
Command
Class
Instance
ID
ID
Attribute
ID
09 hex
01 to 20
65 hex
hex
09 hex
01 to 20
65 hex
hex
09 hex
01 to 20
68 hex
hex
09 hex
01 to 20
68 hex
hex
09 hex
01 to 20
66 hex
hex
09 hex
01 to 20
66 hex
hex
09 hex
01 to 20
67 hex
hex
Appendix A
Response
Command data
Service data
Data
---
1 byte
00 hex: Total
ON time
mode
01 hex: Con-
tact opera-
tion counter
mode
1 byte
---
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
4 bytes
---
00000000 to
FFFFFFFF hex
(0 to
4294967295)
---
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
---
---
---
1 byte
00 hex:
Within range
01 hex: Out
of range
(over the
monitor
value)

Advertisement