Omron CRT1 - 10-2008 Operation Manual page 508

Componet slave units and repeater unit
Table of Contents

Advertisement

Temperature Input Unit Functions
Stabilization Times
required in Each Step
Input Unit's power supply ON
Wiring for input 0 adjustment
Input 0 upper/lower limit adjustment
Input 0 bias compensation
Change wiring for input 1 adjustment
Input 1 upper/lower limit adjustment
Input 1 bias compensation
Change wiring for input 2 adjustment
Input 2 upper/lower limit adjustment
Input 2 bias compensation
Change wiring for input 3 adjustment
Input 3 upper/lower limit adjustment
Input 3 bias compensation
(End of adjustment)
Note
The following diagram shows the stabilization times (waiting times) required
when adjusting all 4 inputs.
Step
(1) The terminal block temperature stabilization time does not affect the up-
per/lower limit adjustment after changing the wiring for input 1, so the ad-
justment can be performed immediately if 30 minutes have passed since
the Temperature Input Unit's power was turned ON.
(2) To perform the adjustment procedure properly, always allow sufficient
time for the temperature to stabilize. Also allow sufficient time for devices
such as the STV, DMM, and ZERO-CON to stabilize. Refer to each de-
vice's operating manual for details.
Timing chart
Wait at least 30 minutes.
(Check whether additional
Temperature
time is required for devices
Input Terminal's
such as the STV, DMM,
stabilization time
and ZERO-CON.)
10 minutes
40 minutes
40 minutes
40 minutes
Section 11-5
Stabilization time
Terminal Block temperature
stabilization time 1 after wiring
Terminal Block temperature
stabilization time 2 after wiring
is changed
Terminal Block temperature
stabilization time 3 after wiring
is changed
Terminal Block temperature
stabilization time 4 after wiring
is changed
485