Parameterizing Using The Bop20 (Basic Operator Panel 20) - Siemens SINAMICS DCM Operating Instructions Manual

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Operation

9.2 Parameterizing using the BOP20 (Basic Operator Panel 20)

9.1.5.5
Information on BICO technology
Binector-connector converters and connector-binector converters
Binector-connector converter
● Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
word.
● p2080[0...15] BI: PROFIdrive PZD send bit-serial
Connector-binector converter
● A 32-bit integer double word or a 16-bit integer word is converted to individual digital
signals.
● p2099[0...1] CI: PROFIdrive PZD selection receive bit-by-bit
Fixed values for interconnection using BICO technology
The following connector outputs are available for interconnecting any fixed value settings:
● p2900[0...n] CO: Fixed value_%_1
● p2901[0...n] CO: Fixed value_%_2
● p2930[0...n] CO: Fixed value_M_1
Example:
These parameters can be used to interconnect the scaling factor for the main setpoint or to
interconnect an additional torque.
9.2
Parameterizing using the BOP20 (Basic Operator Panel 20)
9.2.1
General information about the BOP20
The BOP20 can be used to power drives up and down during the commissioning phase as
well as display and modify parameters. Faults can be diagnosed as well as acknowledged.
336
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics dc master

Table of Contents