Siemens SINAMICS DCM Operating Instructions Manual page 63

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

10 Shields for analog signal cables may be connected to ground at both ends if equipoten-
11 Ensure that the RFI suppression filter is always located close to the suspected source of
12 RFI suppression filters must be used in order to conform to limit value class A1.
13 A line reactor must be included in the field circuit for controlled field power supplies.
14 A line reactor must be included in the armature circuit of the converter.
15 The motor cables do not have to be shielded. There must be a clearance of at least
Footnotes
1)
2)
Cabinet configuration and shielding
Figure 6-3
Shielding at control cabinet inlet
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
tial bonding is good (this must be done over a large area with good conductivity). It can
be assumed that equipotential bonding is good if all metal parts are well interconnected
and the electronics components are supplied from a single source.
Connecting a shield at one end prevents low-frequency, capacitive interference from
being coupled in (e.g. 50 Hz hum). In this case, the shield should be connected in the
control cabinet; a sheath wire may also be used for this purpose.
The cable to the temperature sensor on the motor (X177:53 to 55) must be shielded.
The shield must be connected to ground at both ends.
interference. The filter must be attached to the cabinet enclosure, mounting plate, etc.,
over a flat area. Incoming and outgoing cables must be physically separated.
Additional loads must be connected upstream of the filter (on the line side).
The controller used and the manner in which the rest of the control cabinet is wired will
determine whether an additional line filter needs to be installed.
20 cm between the line supply feeder cable and the motor cables (field, armature).
Use a partition if necessary.
Signal cables are defined as:
Digital signal cables: e.g. cables for incremental encoders
Analog signal cables: e.g. ±10 V setpoint cable
Serial interfaces: e.g. PROFIBUS-DP
Generally speaking, "ground" refers to all metallic conductive parts that can be
connected to a protective conductor, such as the cabinet enclosure, motor enclosure or
foundation ground.
6.1 Instructions for EMC-compliant drive installation
Connecting
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics dc master

Table of Contents