Siemens SINAMICS DCM Operating Instructions Manual page 385

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Bit
Meaning
11
1 = setpoint inversion
12
Reserved
13
1 = Motorized
potentiometer, higher
14
1 = Motorized
potentiometer, lower
Note:
If "Motorized potentiometer, higher" and "Motorized potentiometer, lower" are both 0 or 1 at the same time, the
current setpoint is frozen.
15
1 = CDS bit 0
(only with telegrams
p0922 = 20!)
Reserved
STW2 (control word 2)
See function diagram [2444].
Table 10- 9
Control word 2 (STW2)
Bit
Meaning
0
Drive data set selection DDS, bit 0
1
Drive data set selection DDS, bit 1
2 to 11
Reserved
12
Master sign-of-life bit 0
13
Master sign-of-life bit 1
14
Master sign-of-life bit 2
15
Master sign-of-life bit 3
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
Explanation
1: Setpoint is inverted
0: The setpoint is not inverted
Only when p0922 = 1 or 352, otherwise reserved
Only when p0922 = 1 or 352, otherwise reserved
1: Command data set changeover (CDS) bit 0 is
active.
0: Command data set changeover (CDS) bit 0 is
inactive.
When p0922 = 1 or 352
Descriptions of functions
10.3 Communication according to PROFIdrive
Operating
condition
-
-
-
-
-
-
Interconnection parameter
p0820[0] = r2093.0
p0821[0] = r2093.1
-
p2045 = r2050[3]
BICO
BI: p1113
-
BI: p1035
BI: p1036
BI: p0810
-
383