Final Confirmation; Optimization Runs; Status After Commissioning - Siemens SINAMICS DCM Operating Instructions Manual

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Commissioning
8.4 Commissioning using the AOP30 Operator Panel

Final confirmation

Confirm the parameters you have entered to save them. Once you have selected "Next" and
activated your entries with <F5>, the parameters you entered will be permanently saved and
the calculations required for closed-loop control carried out.

Optimization runs

Perform the optimization runs one after the other:
To navigate through the selection fields, choose <F2> or <F3>.
To activate a selection, choose <F5>.
p50051 = 23
p50051 = 24
p50051 = 25
p50051 = 26
p50051 = 27
p50051 = 28
p50051 = 29
For further details, see Chapter "Drive optimization (Page 303)".
If an optimization run is not carried out, the motor control uses the motor characteristic
values calculated from the rating plate data rather than the measured values.
Unexpected motor movement during optimization runs
Optimization runs cause movement of the drive which can result in death, severe injury or
material damage.
• Observe the general safety instructions.
• Ensure that the EMERGENCY STOP functions are fully functional when commissioning
8.4.2

Status after commissioning

LOCAL mode (control via operator panel)
● You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
● Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
● You can set the setpoint using the "Increase" and "Decrease" keys or by entering the
appropriate numbers on the operation screen using the numeric keypad.
252
Optimization of armature current control for inductive load
Optimization of closed-loop field-current control
Optimization of closed-loop armature current control
Optimization of speed control
Optimization of closed-loop EMF control (incl. field characteristic plotting)
Plotting the friction characteristic
Optimization of closed-loop speed control for drives with a mechanical
system capable of oscillation
WARNING
the drive.
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A