Siemens SINAMICS DCM Operating Instructions Manual page 147

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Table 6- 33
Firing pulse module connections
Terminal,
Function
connection
XIMP_1 control for firing pulse transformers for the thyristors
IMP11
For thyristor V11
P24
IMP12
For thyristor V12
P24
IMP13
For thyristor V13
P24
IMP14
For thyristor V14
P24
IMP15
For thyristor V15
P24
IMP16
For thyristor V16
P24
XIMP_2
Same as XIMP_1
The terminals on terminal strip XIMP_2 are parallel to the terminals on terminal strip XIMP_1 with the same name.
XIMP_3
Same as XIMP_1
The terminals on terminal strip XIMP_3 are parallel to the terminals on terminal strip XIMP_1 with the same name.
XIMP_4 control for firing pulse transformers for the thyristors
IMP21
For thyristor V21
P24
IMP22
For thyristor V22
P24
IMP23
For thyristor V23
P24
IMP24
For thyristor V24
P24
IMP25
For thyristor V25
P24
IMP26
For thyristor V26
P24
XIMP_5
Same as XIMP_4
The terminals on terminal strip XIMP_5 are parallel to the terminals on terminal strip XIMP_4 with the same name.
XIMP_6
Same as XIMP_4
The terminals on terminal strip XIMP_6 are parallel to the terminals on terminal strip XIMP_4 with the same name.
XIMP11 control for firing pulse transformers for the thyristors
IMP11
For thyristor V11
P24
X11
G, K
Firing cable, thyristor V11
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
6.16 Connector assignment (terminals, Faston mounting tabs, ribbon cables)
Technical data, comments
If the firing pulse transformer module is divided up (please refer to the
section titled "Removal/Installation and division of modules"), the
controls for the firing pulse transformers must be routed via these
terminal connections.
This involves making the following connections:
XIMP_1 - IMP11 → XIMP11 - IMP11 (for thyristor V11)
XIMP_1 - P24 → XIMP11 - P24 (for thyristor V11)
XIMP_1 - IMP12 → XIMP12 - IMP12 (for thyristor V12)
XIMP_1 - P24 → XIMP12 - P24 (for thyristor V12)
etc.
If the firing pulse transformer module is divided up (please refer to the
section titled "Removal/Installation and division of modules"), the
controls for the firing pulse transformers must be routed via these
terminal connections.
This involves making the following connections:
XIMP_4 - IMP21 → XIMP21 - IMP21 (for thyristor V21)
XIMP_4 - P24 → XIMP21 - P24 (for thyristor V11)
XIMP_4 - IMP22 → XIMP22 - IMP22 (for thyristor V22)
XIMP_4 - P24 → XIMP22 - P24 (for thyristor V12)
etc.
Only to be connected if the firing pulse transformer module is divided
up (see terminal strip XIMP_1)
Firing pulse (see below) gate (G) to auxiliary cathode (K)
Connecting
145