Connecting
6.16 Connector assignment (terminals, Faston mounting tabs, ribbon cables)
6.16.8

Firing pulse

Time sequence
The time sequence for firing pulses is set via parameter p51826:
p51826[0]
p51826[1]
p51826[2]
Notes
● If p51826[0] = 105 or p51826[1] = 105: Block pulse (without pulse chopping)
● If p51826[0] ≤ p51826[1] is set, p51826[0] will be ignored and the first pulse will have the
same length as all the other pulses.
● p50079 is used for short pulse/long pulse selection.
p50079 = 0
p50079 = 1
Figure 6-45
The pulse shape of the current depends on the length of the cable to the thyristor
(cathode/gate). Cable inductance causes the rising edge of the current pulse to become
slower as the cable length increases.
148
Length of first pulse (factory setting = 50 µs)
Length of other pulses (factory setting = 35 µs)
Length of pause (factory setting = 70 µs)
Short pulses, pulse length 890 µs
Long pulses, pulse duration up to approx. 0.1 ms before the next pulse
Firing pulse - time sequence
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A